• 12kV SIRING Solid Dielectric Integrated VCB
12kV SIRING Solid Dielectric Integrated VCB
+

Share to

12kV SIRING Solid Dielectric Integrated VCB

SIRING® series solid insulation switch modules, together with reliable, universal and modular breaker spring operating mechanism and three-station operating mechanism, constitute SIRING® series solid insulation switch units. The operating mechanism, which has passed the type test, is a mature and reliable product with many years of operation experience, and all its technical parameters meet the code requirements and the standards of electric power industry and power grids. 

For more details, please Contact!

Product application

Classification

keyword

  • Product Description
  • SIRING® series solid insulation switch modules, together with reliable, universal and modular breaker spring operating mechanism and three-station operating mechanism, constitute SIRING® series solid insulation switch units. The operating mechanism, which has passed the type test, is a mature and reliable product with many years of operation experience, and all its technical parameters meet the code requirements and the standards of electric power industry and power grids. 

    Reliable circuit breaker + three-station operating mechanism: the circuit breaker mechanism has passed 10000 times test and the three- station mechanism has passed 5000 times life test. 

    The solid insulation module and the mechanism are factory-pre-assembled, and hoisted into the cabinet as a whole, facilitating assembly and maintenance. 

    The circuit breaker mechanism can be manually + electrically operated, and the three-station mechanism can be manually + electrically operated, facilitating the automation of power grid.

     

    SIRING®  Technical Specification

    ltem

    Unit

    Data

    Rated Voltage

    kV

    12

    Rated Frequency

    Hz

    50/60

    Rated Current

    A

    630/1250/1600/2000/2500/3150/4000*

    Rated 1min Power-frequency withstand voltage (Phase/ Distance)

    kV

    42/48

    Rated lighting impulse withstand voltage (Phase/ Distance)

    kV

    95/95

    Short-circuit Current Breaking Capacity

    kA

    25/31.5/40

    Rated Making Capacity

    kA

    63/80/100

    Rated Short-time Withstand Current

    kA

    25/31.5/40

    Peak Withstand Current

    kA

    63/80/100

    Rated Short-time Withstand Current Duration

    s

    4

    Electrical Endurance of Circuit Breaker

    times

    Class E2:≥30

    Mechanical Endurance of Circuit Breaker

    times

    Class M2:≥10000

    Mechanical Endurance of Load Switch

    times

    ≥5000

    Mechanical Endurance of Ground Switch

    times

    ≥5000

    Rated Voltage of Control Loop

    V

    AC110/220 DC110/220